I NSTALLATION M ANUAL September 2009 Document #: LT-2010 Rev.2 WARNING : This manual contains information on limitations regarding product use and
4Addressable Input CircuitsThere are two classes of addressable input circuits supported by the Control Unit:• "Class A" (Style 6) - This is
MR-2900 Installation Manual51.6 Terminal BoardField connections are terminated on the MR-2936 Terminal Board, which in addition to terminal blockscont
61.8 Power SupplyThe Power Supply (MR-2905) is rated at 8A unregulated, providing the system with primary DC power. It iscomplete with a battery charg
MR-2900 Installation Manual7For NFAPA Style 7 connection of the network, port 1 of node 1 is connected to port 2 of node 2. Port 1 ofnode 2 is connect
82.0 Installation2.1 Unpacking the MR-2900The basic MR-2900 package includes the following components:BackboxOuter door including:•Lock• Display windo
MR-2900 Installation Manual92.2 Mounting and Assembling the MR-2900Surface and Flush MountingThe MR-2900 can be mounted in either flush or surface mou
102.3 Internal Assembly• Attach AC wiring to the AC Terminal Block. Attach green ground wire to ground screw onbackplate.• Place the batteries in the
MR-2900 Installation Manual11Figure 4: Back Box Dimension and Knockout Reference29-1/2"(750 mm)14-1/2" (368 mm)27-1/2"(699 mm)1-1/4&quo
122.4 WiringPower ConnectionsThe Main Control Unit requires an AC power supply. See Figures 5 and 6 below.The batteries forming the Battery Pack are w
MR-2900 Installation Manual13Conventional Style D (Class A) CircuitThis is a 4-wire power-limited and supervised StyleD (Class A) initiating device ci
14Normally Closed CircuitThis is a 2-wire non-supervisory circuit and issupported by the MR-2928 module. This circuit islisted by UL for connection to
MR-2900 Installation Manual15Addressable Style 6 (Class A) CircuitThis is a 4-wire power-limited and supervised Style 6 (ClassA) communications circui
16Addressable ModulesThe addressable module extended circuits are wired as shown on the next page in Figures 15 - 20.Figure 15: MRI-M500M WiringFigure
MR-2900 Installation Manual17Figure 17: MRI-M502M WiringFigure 18: MRI-M500S Wiring for Signalling Circuits
18Style Y (Class B) Bell CircuitThis is a 2-wire Style Y (Class B) power-limited andsupervised signalling (notification appliance) circuit.Devices and
MR-2900 Installation Manual19Style Z (Class A) Bell CircuitThis is a 4-wire Style Z (Class A) power-limited andsupervised signalling (notification app
20Inner Door Ribbon CablesTwo ribbon cables connect the Terminal Board to the MainCircuit Board. These cables are on the hinged side of theInner Door
MR-2900 Installation Manual21Table 5: Maximum Capacitance for Network Baud RatesRS-232 Network WiringRS-232 Network wiring uses three (3) wires betwee
22Annunciator, UDACT and Reverse Polarity WiringThe MR-2614 and MR-2644 Annunciators, the MR-2900-CITY Reverse Polarity module and the MR-2900-DACT Di
MR-2900 Installation Manual233.0 Technical SpecificationsElectrical RatingsAC Line Voltage 120 V, 60 Hz / 240 V, 50 Hz2A / 1AAC Brownout@120V 90 VAC N
MR-2900 Installation ManualiTable of Contents1.0 Technical Information ...
24Bell (Notification Appliance) CircuitsNumber & Type 8 Class B, NFPA Style Y/ Class A, NFPA Style ZSupervisory Current 1.0 mA, power limitedAlarm
MR-2900 Installation Manual254.0 Parts ListModel DescriptionBasic Control UnitMR-2900 Basic Control Unit (with or without MR-2920 strip printer)Option
265.0 Appendix A: Power Supply and Battery CalculationsÒ See 6.0 Appendix B: ULC Listed Compatible Smoke Detectors on page 28 and 7.0 Appendix C: UL L
MR-2900 Installation Manual275.1 GeneralBatteries are designed and manufactured for a specific use. "Standby" is one of these uses. They are
286.0 Appendix B: ULC Listed Compatible Smoke DetectorsThe following conventional smoke detectors are ULC listed for compatibility with the MR-2900Con
MR-2900 Installation Manual29Simplex Fenwal2098-9110 PSD-7131/70-201000-001 42EdwardsPSD-7131/70-201000-002 426249C 100 PSD-7131/70-201000-003 426250C
306.1 ULC Listed Compatible Addressable DevicesModel DescriptionTypical CurrentDraw µAMRI-1251 Ionization type smoke detector 300MRI-1251B Ionization
MR-2900 Installation Manual317.0 Appendix C: UL Listed Compatible Devices7.1 UL Listed “Class B” Smoke DetectorsThe following Listed 2-wire smoke dete
32Fenwal CPD-7023 I3FE1 CPD-001 FE01A 80 μACPD-7023 I3FE1 CPD-002 FE02A 80 μACPD-7023 I3FE1 CPD-003 FE03A 80 μACPD-7023 I3FE1 CPD-005 FE05A 80 μACPD-7
MR-2900 Installation Manual33Gentex 224 -1 N/A N/A224-25 -1 N/A N/AHochiki SIF-24F HD-2 HS-221D HB-4 102 μASIF-24F HD-2 YBA-M221 HB-4 102 μASIH-24F HD
347.2 UL Listed “Class A” Smoke Detectors The following Listed 2-wire smoke detectors and bases are compatible with the MR-2900 Control Panelusing the
MR-2900 Installation Manual357.3 UL Listed Notification AppliancesThe following notification appliances, where a current rating is shown, may be used
36CH-CF1-WS-24-CF-W Strobe Chime 20 25CH-DF1-WS-24-VF-R Strobe Chime 20 25CH-DF1-WM-24-VF-R Strobe Chime 20 8846T-G6-24-WS-24-HF-R Strobe Bell, 6 in.
MR-2900 Installation Manual37AMT-24-LSM Multitone Strobe Signal, non sync 48 115AMT-24-MS Multitone Strobe Signal, non sync 48 135AMT-24-IS Multitone
38RSS-2415C Strobe - 70RSS-243OC Strobe - 107RSS-2475C Strobe - 215RSS-24100C Strobe - 250RSSP-2415C Strobe, retrofit plate - 70RSSP-2430C Strobe, ret
MR-2900 Installation Manual39GX90S-4-60 Piezo Horn/Strobe 60 cd 130 (combined)GX90S-4-110 Piezo Horn/Strobe 110 cd 235 (combined)GXS-4-15 Strobe 15 Cd
40P241575 (R) (W) Horn/Strobe 39 64P2475 (R) (W) Horn/Strobe 39 159P24110 (R) (W) Horn/Strobe 39 191P241575K Horn/Strobe 39 64P2475K Horn/Strobe 39 15
MR-2900 Installation Manual41SS241575ADAS Strobe - 180MASS2415ADAS Horn/Strobe 59 125MASS241575ADAS Horn/Strobe 59 180RP2415ADA Strobe - 90RP241575ADA
427.5 UL Listed Analog Addressable DevicesThe following Listed analog addressable smoke detectors, detector bases, monitor modules, controlmodules and
MR-2900 Installation Manual437.6 UL LIsted Compatible Door Holder/ReleasersThe following listed door holders are compatible with the MR-2900 and MR-24
MR-2900 Installation ManualiiiList of Figures and TablesFigure 1: Basic Network Communication Flow ...
448.0 Appendix D: Interconnection to Other Equipment8.1 Radionics 2071C and 2071ACThe wiring between the MR-2900 and the Radionics 2071C and 2071AC Di
MR-2900 Installation Manual458.2 Silent Knight 5104The wiring between the MR-2900 and the Silent Knight 5104 Dialer is as shown in the following diagr
468.3 CTM City Tie ModuleThe CTM is designed to interface between a control panel and a local city tie box. The interface from thecontrol panel is via
MR-2900 Installation Manual478.4 Keltron 3158 TTMThe Keltron 3158 TTM and the MR-2900 are wired together as shown below:Addressable control modules ca
9.0 Warranty & Warning Information489.0 Warranty & Warning Information9.1 Warning Please Read Carefully Note to End Users: This equipment is s
MR-2900 Installation Manual49breakdowns, interruptions, loss, destruction, alteration or other problems in the use of a product arising our of, or cau
9.0 Warranty & Warning Information509.2 Limited Warranty Secutron Inc. warrants the original purchaser that for a period of two years from the dat
MR-2900 Installation Manual519.5 Out of Warranty Repairs Secutron Inc. will at its option repair or replace out-of-warranty products which are returne
© 2009 Secutron, Inc. Canada 25 Interchange Way Vaughan, ON L4K 5W3 Tel: (888) SECUTRON (888) 732-8876 Fax: (905) 660-4113 U.S.A4575 Witmer Indus
MR-2900 Installation Manual11.0 Technical Information1.1 GeneralThe MR-2900 Fire Alarm Control Unit provides capability for up to 24 Input Circuits, 8
2Communication PortsThe Control Unit has 6 communication ports available:• Port #1- network (Proprietary)• Port #2- network (Proprietary)• Port #3- ge
MR-2900 Installation Manual31.3 Front PanelThe system controls consist of 12 system switches and a 20position alphanumeric keypad. The 12 system switc